首页|Switching Transients in Constrained Transformer-Line/Cable Configurations

Switching Transients in Constrained Transformer-Line/Cable Configurations

Switching Transients in Constrained Transformer-Line/Cable Configurations

来源:Arxiv_logoArxiv
英文摘要

This paper investigates the transient phenomena that occur in two special cases in the Netherlands: (A) during the energization of a power transformer via a cable feeder and (B) the energization of a power transformer together with an overhead line (OHL). In Case A a 7 km long 150 kV cable and a 150/50 kV transformer are connected and energized at the same time. In Case B a 150/50 kV transformer and a short 50 kV OHL are connected and energized simultaneously. The reason behind this kind of situations is related to space restrictions and cost efficiency.

Y. Xiang、L. Wu、K. Velitsikakis、A. L. J. Janssen

变压器、变流器、电抗器输配电工程高电压技术

Y. Xiang,L. Wu,K. Velitsikakis,A. L. J. Janssen.Switching Transients in Constrained Transformer-Line/Cable Configurations[EB/OL].(2025-04-30)[2025-06-03].https://arxiv.org/abs/2504.21594.点此复制