On the input admittance of a universal power synchronization controller with droop controllers
On the input admittance of a universal power synchronization controller with droop controllers
Recent work has proposed a universal framework that integrates the well-established power synchronization control into vector current control. Using this controller for the parallel operation of grid-forming converters, and/or with loads that have strong voltage magnitude sensitivity, requires additional loops manipulating the voltage magnitude, e.g., $QV$ and $PV$ voltage-power droop controllers. This paper derives the input admittance of the resulting overall scheme. Sensitivity analyses based on the passivity index demonstrate the benefits of the proportional components of $QV$ and $PV$ control. A case study is presented where a grid-forming converter is operated in parallel with a generator.
Orcun Karaca、Irina Subotic、Lennart Harnefors、Ioannis Tsoumas
电工基础理论变压器、变流器、电抗器输配电工程
Orcun Karaca,Irina Subotic,Lennart Harnefors,Ioannis Tsoumas.On the input admittance of a universal power synchronization controller with droop controllers[EB/OL].(2025-06-20)[2025-07-02].https://arxiv.org/abs/2506.17044.点此复制
评论