|国家预印本平台
首页|隔离开关电弧模型及其对VFTO的影响

隔离开关电弧模型及其对VFTO的影响

rcing model of GIS switching and its effect on VFTO

中文摘要英文摘要

在VFTO计算中,隔离开关电弧的准确建模,是影响VFTO计算精度的关键因素。在对比分析现有电弧模型的基础上,提出一种动态电弧模型,将电弧电阻将电弧分为电弧电流过零前和电弧电流过零后两个阶段,采用时变电阻和mayer模型相结合描述电弧的动态过程,利用matlab/simulink建立电弧模块,并结合某 1000kV电站的实际电路,详细计算动态电弧模型下 GIS 内部的 VFTO。结果表明,动态电弧模型充分考虑了电弧发展过程,对于提高VFTO仿真计算结果的准确性有着重要意义。

In computational process of very fast transient over-voltage(VFTO), it is essential to find the accurate model of the gas insulated substation(GIS). The arcing model of disconnector is particularly important. The general arc-resistance model in not available to give better simulation for the changing of status during the development of arc.In the paper, based on the sical process of arc and the analysis of existing arc model: the exponential time-varying resistance and segmental arcing model,Dynamic arcing model is proposed,which is divided into two stages before arc current zero and after arc current zero. Dynamic arcing model combine time-varying resistance and mayer model to describe the dynamic process of arc. Create the arc model blockset upon matlab/simulink software platform, calculating a 1100kV GIS internal VFTO on the condition of dynamic arcing model. It is indicated that the sical process of arc is modeled precisely by the dynamic arcing model, and it is useful to improve the accuracy of VFTO simulation.

王娜、林莘、徐建源

高电压技术电器

高电压工程隔离开关动态电弧模型气体绝缘变电站快速暂态过电压

High Voltage Engineeringdisconnectordynamic arcing modelgas insulated substationvery fast transient over-voltage

王娜,林莘,徐建源.隔离开关电弧模型及其对VFTO的影响[EB/OL].(2011-11-15)[2025-08-11].http://www.paper.edu.cn/releasepaper/content/201111-250.点此复制