有源滤波器死区的脉冲直接补偿
he direct pulse compensation of APF
由于开关器件死区时间的存在,逆变器输出的补偿电流波形产生误差,使得有源滤波器补偿效果变差。针对空间矢量电流控制的开关周期固定且PWM脉冲对称的特性,提出了一种无需过零检测电路的脉冲直接补偿死区方法,该方法通过在与IGBT状态切换时间点相比较的三角载波上叠加一个与三角波同频率,幅值与死区时间相等的方波,对PWM脉冲进行补偿,从而抵消死区时间带来的影响,该方法非常简单有效。MATLAB仿真表明该方法基本实现了死区时间的完全补偿。
s the presence of the dead time of switching device ,the compensation current of the inverter will have errors , and the compensation effect of active power filter becomes poor. For the fixed switching cycle of space vector current control and symmetrical PWM pulse, proposed a direct pulse compensation method of dead-time without zero-crossing detection circuit .It offsets the impact of dead time by superimposed a square wave on the triangular carrier which compared to the IGBT switching time, the triangular carrier and the square wave have the same frequency ,and the amplitude of square wave is equal to dead time. The method is very simple and effective. MATLAB simulation shows that the method basically achieves full compensation of dead time.
李钢、胡欠欠
变压器、变流器、电抗器电器
有源滤波器空间矢量控制死区脉冲直接补偿法。
ctive Power FilterSpace vector controlDead-timeDirect pulse compensation.
李钢,胡欠欠.有源滤波器死区的脉冲直接补偿[EB/OL].(2010-08-30)[2025-08-16].http://www.paper.edu.cn/releasepaper/content/201008-454.点此复制